Analog Electronic Modules
Use of PTC resistors
PTCs are suitable for temperature monitoring and as thermal protective devices for
complex drives and transformer windings.
• Select "Two-conductor resistor" and "PTC" at parameter assignment:
• Connect the PTC in accordance with the two-conductor connection method.
• Apply PTC resistors of type A (PTC thermistors) in accordance with DIN /
VDE 0660, Part 302.
• Sensor data for the PTC resistor:
Feature
Switching points
(TNF–5) _C
(TNF+5) _C
(TNF+15) _C
Measuring voltage
Voltage on the
PTC
13-86
Technical
specifications
On/reset
Max. 750 W
Off
From 1650W to 4000W
On/reset
From 1650W to 750W
Max. 550W
Min. 1330W
Min. 4000W
Max. 7.5 V
Remarks
Measured resistance < response
threshold
SIMATIC S7: bit 0 = "0" (in the PII)
SIMATIC S5: bit 3 = "0" (in the PII)
Temperature increase
Measured resistance > response
threshold
SIMATIC S7: bit 0 = "1" (in the PII)
SIMATIC S5: bit 3 = "1" (in the PII)
Temperature decrease
Measured resistance < response
threshold
SIMATIC S7: bit 0 = "0" (in the PII)
SIMATIC S5: bit 3 = "0" (in the PII)
TNF= rated operating temperature