Appendix
A.1 Data formats and data sets
A.1.19
I&M data
The following I&M (identification & maintenance function) data is supported by all M200D
PROFIBUS/PROFINET motor starters:
Number
I&M 0
I&M 1
I&M 2
I&M 3
Note
With PROFINET, the I&M data can be accessed via data sets 0xAFF0 - 0xAFF3 (PNO).
A.1.19.1
DS231 Read device identification
PROFIBUS: I&M 0
The following data is saved in data set DS 231:
Byte
0 ... 9
10 ... 11
12 ... 31
32 ... 47
48 ... 49
50 ... 53
54 ... 55
56 ... 57
58 ... 59
60 ... 61
62 ... 63
216
Name
Device identification
Equipment designation
Installation
Description
Length
Content
0x00
Reserved = 0
0x002A
MANUFACTURER_ID
(20 bytes)
ORDER_ID
(16 bytes)
SERIAL_NUMBER
(2 bytes)
HARDWARE REVISION
(4 bytes)
SOFTWARE_REVISION
(2 bytes)
REV_COUNTER
(2 bytes)
PROFILE_ID
(2 bytes)
PROFILE_SPECIFIC_TYPE
(2 bytes)
IM_VERSION
(2 bytes)
IM_SUPPORTED
Remark
As stored in the device initialization
Entered by the user during configuration via the Device
Properties screen form in HW Config
Meaning
I&M header
I&M0 data block 0
42 = Manufacturer ID SIEMENS
Order No. (MLFB)
Serial number
Hardware revision or product version
Firmware version
Provides information about the parameterized
changes on the module. The "REV_
COUNTER" is incremented after each
change.
Gives information about the PROFIBUS
profile supported by the device and the line of
products belonging to the device.
Used to supplement the object "PROFILE_ID"
and contains further information on the
profile.
Provides information about the version of the
identification data (01 01hex = Version 1.1).
Provides information about the available
identification data (Index 2 to 4).
Manual, 08/2014, A5E01577426A/RS-AA/004