Input n action
Different actions can be triggered when an input signal is present. You can parameterze the
following actions dependent on "Input n level", "Input n signal" and "Mode".
Note
If "Input n signal" = retentive and "Input n action" = Motor CW/CCW, at least one input must
always be parameterized with input action "Tripping ... " or "Quick Stop".
If this rule is violated, the motor starter will reject the parameters with the relevant
diagnostics message!
Input n action
No action
Trip without restart
Trip with restart (auto
reset)
Trip end position CW
Trip end position CCW
(RSte/sRSSte only)
Group warning
Manual mode local
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Level
Signal
NO/NC
n-ret./ret.
All
NO/NC
n.ret./-
All
NO/NC
n.ret./-
All
NO/NC
n.ret./-
All
NO/NC
n.ret./-
All
NO/NC
n-ret./ret.
All
NO/NC
n.ret./-
All
Mode
Causes the motor and brake to trip.
Must be acknowledged once the cause of the tripping
has been rectified (initial status).
Causes the motor and brake to trip.
Acknowledged automatically once the cause of the
tripping has been rectified (initial status).
The motor and the brake output are tripped
regardless of the direction of rotation.
The brake output can be switched on again once the
"Brake" and "Motor CW / CCW" control commands
have been canceled.
Trip end position CW rotation: The motor can only be
switched on again with the opposite command
("Motor CCW").
Trip end position CCW The motor can only be
switched on again with the opposite command
("Motor CW").
The "Group warning" message is set.
The motor starter and the brake output are not
tripped!
The input action responds to the active edge of the
ret.:
input signal. Deactivation with a pending active input
signal is thus possible.
Action is deactivated with trip reset.
Control is only possible via "input n action": "Motor
CW" and "Motor CCW" (see below) possible!
Control is not possible over the fieldbus ("Automatic"
mode)!
"Automatic" mode is only possible again if manual
mode local is canceled and "Input n action": "Motor
CW" or "Motor CCW" is not active.
Functions
3.7 System monitoring
Description
-
55