Input n action
Different actions can be triggered when an input signal is present. You can parameterze the
following actions dependent on "Input n level", "Input n signal" and "Mode".
Note
If "Input n signal" = retentive and "Input n action" = Motor CW/CCW, at least one input must
always be parameterized with input action "Tripping ... " or "Quick Stop".
If this rule is violated, the motor starter will reject the parameters with the relevant
diagnostics message!
Input n action
No action
Trip without restart
Trip with restart (auto
reset)
Trip end position CW
Trip end position CCW
(RSte/sRSSte only)
Group warning
Manual mode local
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Level
Signal
NO/NC
n-ret./ret.
All
NO/NC
n.ret./-
All
NO/NC
n.ret./-
All
NO/NC
n.ret./-
All
NO/NC
n.ret./-
All
NO/NC
n-ret./ret.
All
NO/NC
n.ret./-
All
Mode
Causes the motor and brake to trip.
•
Must be acknowledged once the cause of the tripping
•
has been rectified (initial status).
Causes the motor and brake to trip.
•
Acknowledged automatically once the cause of the
•
tripping has been rectified (initial status).
The motor and the brake output are tripped
•
regardless of the direction of rotation.
The brake output can be switched on again once the
•
"Brake" and "Motor CW / CCW" control commands
have been canceled.
Trip end position CW rotation: The motor can only be
•
switched on again with the opposite command
("Motor CCW").
Trip end position CCW The motor can only be
•
switched on again with the opposite command
("Motor CW").
The "Group warning" message is set.
•
The motor starter and the brake output are not
•
tripped!
The input action responds to the active edge of the
ret.:
input signal. Deactivation with a pending active input
signal is thus possible.
Action is deactivated with trip reset.
Control is only possible via "input n action": "Motor
•
CW" and "Motor CCW" (see below) possible!
Control is not possible over the fieldbus ("Automatic"
•
mode)!
"Automatic" mode is only possible again if manual
•
mode local is canceled and "Input n action": "Motor
CW" or "Motor CCW" is not active.
Functions
3.7 System monitoring
Description
-