Configuration / parameterization
5.2 Parameterize
Device parameter
Current limit value
(x 3.125%)
Brake release delay on
starting
Brake holding time on
stopping
Response to overload -
thermal motor model
Trip class
(DSte / RSte, sDSSTe,
sRSSte in startup
mode ≠ direct)
Trip class
(sDSSte / sRSSte in
startup mode = direct)
Recovery time
Prewarning limit motor
heating
Prewarning limit -
remaining time for
tripping
Idle time
Response to overload
temperature sensor
Temperature sensor
Temperature sensor
monitoring
Response to residual
current detection
128
Default setting
600% (Ie ≤ 9 A)
550% (Ie ≤ 9 A)
0 s
0 s
Motor protection (Page 41)
Tripping without restart
CLASS 10
CLASS 10
in startup mode = direct
CLASS 5 (10a)
in startup mode ≠ direct
90 s
0% (= deactivated)
0 s (= deactivated)
0 s (= deactivated)
Tripping without restart
Deactivated
Yes
Trip
Setting range
Ie ≤ 9 A: 125 % ... 600 %
Ie > 9 A: 125 % ... 550 %
Increment: 3.125 %
- 2.5 to + 2.5 s
Increment: 0.01 s
0 to 25 s
Increment: 0.01 s
Tripping without restart
Tripping with restart
Warning
CLASS 5 (10a),
CLASS 10
CLASS 15,
CLASS 20
CLASS OFF
CLASS 5 (10a),
CLASS 10
CLASS OFF
60 to 1800 s
Increment: 30 s
0 ... 95 %
Increment: 5 %
0 to 500 s
Increment: 1 s
0 to 255 s increment: 1 s
Tripping without restart
Tripping with restart
Warning
Deactivated
Themoclick
PTC type A
Yes
No
Warning
Trip
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004