Siemens SIRIUS M200D Manual page 129

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Device parameter
Response to current
limit violation
Lower current limit
Upper current limit
Blocking current
Blocking time
Response to
asymmetry
Asymmetry limit
Input signal extension
Input signal delay
Input 1 level
Input 2 level
Input 3 level
Input 4 level
Input 1 action
Input 2 action
Input 3 action
Input 4 action
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Default setting
System monitoring (Page 48)
Warning
18,75 %
112,5 %
800 %
1 s
Trip
30 %
0 ms
10 ms
Normally open
No action
Configuration / parameterization
Setting range
Warning
Trip
18.75 to 100% of I
e
0% (= deactivated)
Increment: 3,125 %
50 to 400% of I
e
0% (= deactivated)
Increment: 3,125 %
150 to 1000% von Ie
150 ... 800% of Ie
(sDS..., sRS...)
Increment: 50 %
1 to 5 s
Increment: 0.5 s
Warning
Trip
30 ... 60% (0 = deactivated)
Increment: 10 %
0 to 200 ms
Increment: 10 ms
10 ... 80 ms
Increment: 10 ms
Normally closed
Normally open
No action
Trip without restart
Trip with restart
Trip end position CW
Trip end position CCW
(RSte/sRSSte only)
Group warning
Manual operation local
Emergency start
Motor CW
Motor CCW (RSte/sRSSte only)
Quick stop
Trip reset
Cold run
5.2 Parameterize
129