Functions
3.3 Basic functions / parameters
Instructions
● In the motor starter, the rated operating current is preset at the factory to the maximum
value. (For testing at startup without fieldbus and without previous parameterization)
● In the GSD and the "Motor Starter ES" software, the rated operating current is preset to
the minimum value for safety reasons. You must therefore parameterize this value when
you configure the system Otherwise the motor starter would trip when it starts for the first
time due to overloading.
● The rated operating current depends on the "startup mode" parameter on motor starters
with soft starter function. If the startup mode is set as "direct", the choice of rated
operating current is restricted to 9 A.
Settings
Rated operating current
On soft starters (sDSSte, sRSSte) in the startup mode "direct"
1)
Note
The setting range depends on the device type!
28
Device parameter
Default setting
In the motor starter: Maximum value
In GSD/Motor Starter ES: Minimum value
Setting range
0.15 A to 2.0 A
1.5 A to 9.0 A
1.5 A to 12.0 A
Increment: 10 mA
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004