Functions
3.7 System monitoring
Input n action
Emergency start
Motor CW
Motor CCW
(RSte/sRSSte only)
Quick stop
Trip reset
Cold run
NO: NO contact
NC: NC contact
ret: retentive
n.ret: non-retentive (activation and deactivation of the input action follows the status of the input signal (= jog))
56
Level
Signal
NO / -
n.ret./-
All
NO / -
n-ret./ret.
Manual local
NO / -
n-ret./ret.
Manual local
NO/NC
n-ret./ret.
All
NO / -
n.ret./-
All
NO / -
n.ret./-
All
Mode
Starts the motor when an ON command is issued
•
despite the fact that an internal trip command is
present.
Switches on the brake output too if an ON switching
•
command is present for this.
Self-protection of the motor starter remains active
•
and prevents the device from being destroyed.
Only allowed as an NO contact!
•
The motor starter must be in "manual local" mode for
•
these actions.
The device parameters of the braking operation are
•
evaluated.
"Motor CW": Switches the motor and the brake
•
output on and off (clockwise) together.
"Motor CCW": Switches the motor and the brake
•
output on and off (counter-clockwise) together.
Only allowed as an NO contact!
•
The input action is triggered while the active level of
ret.:
the input signal is pending.
Input trigger is deleted by the input action "Quick stop" or
group fault.
The motor and brake output are tripped without a
•
group fault.
"Quick stop" has priority over "Motor CW" and "Motor
•
CCW".
The input action responds to the active edge of the
ret.:
input signal. Deactivation with pending active input
signal is thus possible.
The input trigger is deleted by removal of the control
commands "Motor CW" and "Motor CCW"
"Trip reset" is triggered once
•
Only possible as NO contact!
•
Enables switch-on without main power. If the main
•
power supply is nevertheless present (current
flowing), an internal trip command is generated.
Description
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004