Diagnostics
7.1 Diagnostics with LED
Group fault
SF
LED
Red
Depends on the parameter assignment
1)
Device diagnostics
In the process input image of the starter, any pending group faults (DI 0.2) and group
warning messages (DI 0.3) are transferred cyclically. Further information about the type of
error can be accessed via a diagnostics call (system diagnostics).
All device-specific diagnostics are collected in data set 92 (29 bytes). The content of DS 92
can be read out with the help of "Motor Starter ES" via the device interface or also online via
PROFIBUS/PROFINET with the help of the "Read data set" function.
146
STATE LED
DEVICE LED
Off
Off
Group fault
Device diagnostics pending with enabled group
diagnostics
Thermal motor model overload
Temperature sensor overload
Asymmetry detected
1)
Current limit violation
1)
Connector monitoring
1)
Circuit breaker tripped/switched off
Group fault via input action
Communication module removed from motor starter
module
Manual, 08/2014, A5E01577426A/RS-AA/004