Appendix
A.1 Data formats and data sets
A.1.13

DS95 Read statistics

Object
Byte.Bit
Meaning
No.
607
0
Motor current I
1
Reserved
606
2 ... 3
Last trip current
602
4 ... 7
Operating hours device
603
8 ... 11
Number of starts motor CW
604
12 ... 15
Number of starts motor CCW
605
16 ... 17
Number of overload trips
609
20 ... 23
Motor current I
608
24 ... 27
Last tripping current I
602
28 ... 31
Operating hours motor
611
32 ... 35
Operating hours motor current
= 18 to 49.9% of I
612
36 ... 39
Operating hours motor current
= 50 to 89.9% of I
613
40 ... 43
Operating hours motor current
= 90 to 119.9 % of I
614
44 ... 47
Operating hours motor current
= 120 to 1000% of I
616
50 ... 51
Number of switching element
overload trips
618
54 ... 55
Number of short-circuit trips
619
56 ... 59
Number of stops with mechanical
braking
621
64-67
Number of starts output 1
622
68-71
Number of starts output 2
625
80-83
Number of starts output BO
626
84-87
Maintenance timer
Special feature of operating hours
1)
The motor starter records 2 operating hour values:
The operating hours of the motor indicate how long the switching elements and thus the motor were switched on.
The operating hours of the device (motor starter) indicate how long the power supply 24 V-NS DC of the motor starter was
switched on.
Both operating hour values are recorded in data set 95 - Read statistics. They are entered in the data field "Operating
hours" alternately at 5-second intervals. The bit "Operating hours selection" specifies which of the two operating hours
values has been transferred.
[0]: Operating hours motor
[1]: Operating hours - device.
The operating hours are recorded in the range from 0 to 16,777,215 minutes in 1-second steps.
BO: Brake output
2)
206
Value range/[encoding]
0 ... 797 %
max
0 ... 1 000 % / [unsigned 16]
0 ... 16777215 / [unsigned 32]
0 ... 16777215 / [unsigned 32]
0 ... 16777215 / [unsigned 32]
0 ... 65535 / [unsigned 16]
0 ... 20000 A / [signed 32]
max (rms)
0 ... 20000 A / [signed 32]
A(rms)
0 ... 4 294 967 295 / [unsigned 32]
0 ... 4 294 967 295 / [unsigned 32]
emax
0 ... 4 294 967 295 / [unsigned 32]
emax
0 ... 4 294 967 295 / [unsigned 32]
emax
0 ... 4 294 967 295 / [unsigned 32]
emax
0 ... 65535 / [unsigned 16]
0 ... 65535 / [unsigned 16]
0 ... 4 294 967 295 / [unsigned 32]
0 ... 4 294 967 295 / [unsigned 32]
0 ... 4 294 967 295 / [unsigned 32]
0 ... 4 294 967 295 / [unsigned 32]
0 ... 4 294 967 295 / [unsigned 32]
Increment Relevant for
3.125 %
3.125 %
1 min
1
1
1
0.01 A
0.01 A
1 s / 1 min
1 s / 1 min
1 s / 1 min
1 s / 1 min
1 s / 1 min
1
1
1
1
1
1
1 s
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
All
All
All
1)
All
.RS... only
All
All
All
All
All
1)
All
1)
All
1)
All
1)
All
All
All with BO
2)
All
All
All with BO
2)
All