Siemens SIRIUS M200D Manual page 72

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Functions
3.11 Trace functions
Trigger event
The motor starter supports the following trigger events:
● No trigger event (= deactivated)
● Restart (Power ON)
● Group fault/group warning/group prewarning
● Beginning/end startup
● Beginning/end coasting down
● Input IN1 to IN4
● Output OUT1/OUT2
● Output BO
● Motor CW/motor CCW
● Brake
● Trip reset
● Emergency start
● Self-test
● Cold run
Only when starting with braking output
1)
Note
The trigger event affects all 4 channels in common, that is, they cannot be triggered
differently.
Trigger edge
With the help of this parameter, triggering can take place at a positive signal edge or an
incoming event, or at a negative edge or outgoing event.
Trace start monitor
The recording can be started in two different ways:
● Trace start by command
The trace function can only be started with the help of the trace command.
● Automatic trace start
The recording is started automatically at switch-on or restart with the currently saved
trace parameter values. Otherwise, the trace function behaves in the same way as "Start
by command".
72
(physical braking output)
1)
1)
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004