DEVICE LED (possible colors: red / green / yellow / OFF)
Status
Off
Green
Flashing green
Green flashing
(0.25 s on / 1.75 s off)
Yellow
Flashing yellow
Red
Flashing red
Flickering red
Depends on the parameter assignment
1)
BF/RUN LED (possible colors: red / green / OFF)
Status
Off
Green
Red
Flashing red
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Meaning
Device not ready
Device OK
Device not starting
Energy-saving mode
active
Internal trip
Group warning
Device defective
Firmware updates
Self-test
Self-test
Factory settings
Meaning
Device not in data
exchange or CPU / master
in Stop
Device in data exchange
Bus error
Parameterization error
Configuration error
7.1 Diagnostics with LED
Possible cause
System error:
No electronics supply voltage (DC24V-NS)
or supply is < 18 V
Start-up parameters missing
No start-up parameters received
Group warning due to:
Thermal motor model overload
Temperature sensor overload
Asymmetry detected
Current limit violation
Connector monitoring
Circuit breaker tripped/switched off
Group warning via input action
Maintenance timer limit violation
Motor current flowing
No current flow
Possible cause
e.g. motor starter module disconnected
Fieldbus interface unclear
Incorrect or invalid parameters received
Diagnostics
1)
1)
1)
1)
1)
1)