Commissioning

6.1
Commissioning
The motor starter is parameterized using the PROFIBUS DP/PROFINET IO standard
procedure at startup. Modification of parameters and HMI (human machine interfacing) can
take place during operation, either via the bus and the acyclic mechanism or locally via the
optical device interface.
The "Group diagnostics" parameter can be parameterized to block or enable. If block is
selected, error messages are not sent.
A device error can only be acknowledged by switching the power off and then on again. If
faults are repeated, the motor starter is defective.
All other faults can be acknowledged via trip reset.
Note
Please be sure to note the voltage tolerance for the load voltage supply (contactors and
power electronics) to 55 °C: 20,4 V to 28,8 V.
Current setting
On the motor starter, you parameterize the setting current using the Motor Starter ES
software, GSD/GSDML file (device master data file) or HSP.
Unplug the load from the mains.
You can actuate the integral disconnecting means in the OFF position to disconnect the
motor starter from the mains.
NOTICE
Connecting/disconnecting a load during operation (that is, under power) is not permissible.
Reversing starter
Make sure, via the user program, that before a change of direction, the drive is switched to
"STOP" long enough to come to a standstill.
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004