Run Command; Selecting The Run Command Source - YASKAWA Varispeed CIMR-G7A Instruction Manual

General purpose inverter (advanced vector control) 200v/400v class 0.4 to 110/300 kw (1.2 to 160kva) (1.04 to 460kva)
Hide thumbs Also See for Varispeed CIMR-G7A:
Table of Contents

Advertisement

Run Command

This section explains input methods for the Run Command.

Selecting the Run Command Source

Set constant b1-02 to select the source for the Run Command.
Related Constants
Con-
stant
Number
b1-02
Performing Operations Using a Digital Operator
When b1-02 is set to 0, you can perform Inverter operations using the Digital Operator keys (RUN, STOP,
JOG, and FWD/REV). For details on the Digital Operator, refer to Chapter 3 Digital Operator and Modes.
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, you can perform Inverter operations using the control circuit terminals.
Performing Operations Using a 2-wire Sequence
The factory setting is set to a 2-wire sequence. When control circuit terminal S1 is set to ON, forward opera-
tion will be performed, and when S1 is turned OFF, the Inverter will stop. In the same way, when control cir-
cuit terminal S2 is set to ON, reverse operation will be performed, and when S2 is turned OFF, the Inverter
will stop.
-8
6
Name
Description
Display
Operation
Set the Run Command input method
method
0: Digital Operator
selection
1: Control circuit terminal (sequence
input)
2: MEMOBUS communications
Run Source
3: Option board
Forward/stop
Reverse/stop
Fig 6.8 2-wire Sequence Wiring Example
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 3
1
No
Q
Inverter
Sequence common
Control Methods
Open-
Open
V/f
loop
Flux
Loop
with
Vec-
Vec-
Vec-
PG
tor
tor
tor
1
2
Q
Q
Q
Q

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents