Wall Requirements; Rack Requirements; Rack Size And Strength; Proper Rack Installation - Juniper BX7000 Hardware Manual

Multi-access gateway
Hide thumbs Also See for BX7000:
Table of Contents

Advertisement

CHAPTER 2: Preparing the Site for Gateway Installation

Wall Requirements

Rack Requirements

Rack Size and Strength

Proper Rack Installation

Cabinet Requirements

20
Wall Requirements
Item or Task
For More Information
Measure distance
"DC Power Specifications" on page 78, "DC
between external power
Power Cable Specifications" on page 78,
sources and gateway
"AC Power Specifications" on page 77, and
installation site.
"DC Power Cable Specifications" on
page 78
Acquire cables and
"BX7000 Multi-Access Gateway Overview"
connectors.
on page 3
The gateway can be installed on solid wall (for example, wood, plastic, concrete, or brick wall).
Ensure that the thickness of the wood and plastic wall on which the gateway can be installed is 1 in.
(2.54 cm). For more information on mounting the gateway on a wall, see "Wall-Mounted
Installation" on page 29.
The following sections describe the rack requirements:
Rack Size and Strength on page 20
Proper Rack Installation on page 20
The gateway is designed for installation in a 19-in. (48.2 cm) rack as defined in Cabinets, Racks,
Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics
Industry Association (EIA) (http://www.eia.org). You can install the gateway either in a 19-in. rack
or 23-in. rack.
The rack rails must be spaced wide enough to accommodate the dimensions of the gateway
chassis: 2.6 in. (6.7 cm) high, 9.44 in. (23.97 cm) deep, and 17.51 in. (44.47 cm) wide. The chassis
height of 2.6 in. (6.7 cm) is approximately 1.5 RU. The chassis comes with brackets for use with the
19-in. rack. Prepare the equipment racks by measuring and marking the space for each gateway
you plan to install.
Note: A separate installation kit is provided for 23-in. rack.
To confirm proper equipment rack installation, verify the following:
Racks are installed and electrically grounded according to manufacturer instructions.
Always secure the rack to the structure of the building. If your geographical area is subject to
earthquakes, bolt the rack to the floor. For maximum stability, secure the rack to the ceiling.
Equipment rack installations comply with applicable local, state, and national codes.
The gateway can be installed in an enclosed cabinet with standard 19-in. rack rails. The following
sections describe cabinet requirements:
Cabinet Size and Clearance Requirements on page 21
Cabinet Airflow Requirements on page 21
Performed By
Date
Copyright © 2010, Juniper Networks, Inc.