Setting the IOC Parameters

Use the ED-EQPT command to provision each IOC. This command allows you to
select which IOC is Active and which is Standby; to switch the Active and Standby
IOCs; to place a IOC "In Service" or "Out of Service"; and to define the oscillator type
to Type I or ST3E for a quartz-based IOC or to Type II or ST2 for a Rubidium IOC.
ED-EQPT:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
Note: Type I and ST3E cannot be defined to a Rubidium IOC, and
Type II and ST2 cannot be defined to a quartz-based IOC.
This command has a default access level of ADMIN.
<aid>
<keyword>
IOCm
IOCMODE
m = 1 | 2
IOCACTV
IOCm
IOCSTATE
m = 1 | 2
(cont'd)
CLKTYPE
Sample Command
ED-EQPT::IOC1:TS1000::IOCSTATE=INSERV;
This command places IOC 1 in the "In Service" mode. Use this command when you
have taken an IOC out of service and are now ready to put it back in service.
Autonomous Message
A 1177 REPT EVT
HAS CHANGED,INSRV\"
;
097-58001-02 Revision G – April 2008
<value>
ACTIVE |
STANDBY
n/a
INSRV
OOSRV
ST2/TYPEII |
ST3E/TYPEI
TP-SSU 03-10-24 10:42:40
"IOC1,EQPT:NA,IOCSTATE,NSA,03-10-24 10-42-40:\"IOC STATE
Chapter 4 Provisioning the TimeProvider
Description
Sets the mode of the specified
IOC. For redundant systems,
changing the state of one IOC
forces the other IOC to the
alternate state
Sets the Standby IOC to Active
Places an "Out of Service" IOC in
the "In Service" mode (restarts)
Places an "In Service" IOC in the
"Out of Service" mode. An Out of
Service IOC cannot generate
outputs or monitor inputs and does
not generate alarms
Defines the Local Oscillator type.
Selects the type of clock used to
generate SSMs in Holdover mode
Provisioning the IOC
Default value
ACTIVE
n/a
INSERV
TYPEI
TimeProvider User's Guide 107