Table 4-3. Alarm Conditions and Defaults (Continued)
Description of Alarm
Alarm ID
Condition
INPDISQ
Specified input has
been disqualified or
qualified as a possible
system reference.
INPAIS
The specified input is
receiving an Alarm
Indication Signal.
INPLOS
The specified input has
Loss of Signal.
INPOOF
The specified input is
receiving an Out of
Frame signal.
INPFRQ
Specified input port's
calculated received
frequency exceeds the
pull-in range of the
LO.This alarm condition
disqualifies the input as
a possible reference.
INPPHASE
Specified input port's
phase measurement
exceeds usable value.
INPQL
The received SSM is of
lesser quality than the
provisioned QLEVEL for
a specified input. This
alarm occurs when you
provision the input's
QLEVEL below the
quality level of the LO.
EXDSC
Input has had excessive
discontinuities, indicated
by more than 3 signal
faults (OOF, BPV, CRC,
or AIS) within a 5-minute
window. The alarm
clears when the 5-
minute window contains
less than 3 signal faults.
097-58001-02 Revision G – April 2008
Possible
Alarm
Levels
<aid> = INP1 or INP2
MN | MJ |
CR
MN | MJ |
CR
1
MN | MJ |
1
CR
MN | MJ |
CR
1
NR | NA |
MN | MJ |
CR
2
NR | NA |
MN | MJ |
CR
NR | NA |
MN | MJ |
CR
NR | NA |
MN | MJ |
CR
Chapter 4 Provisioning the TimeProvider
Error
Error
Delay
Delay
Default
Editable?
FLT
Yes
DELAY
IMMED
No
IMMED
No
IMMED
No
IMMED
No
IMMED
No
IMMED
No
IMMED
No
TimeProvider User's Guide 129
Provisioning Alarms
Default Level
SSU
SUB
Mode
Mode
MN
MN
MN
MN
MN
MN
MN
MN
MN
NR
MN
MN
MN
MN
MN
MN

Hide quick links: