Troubleshooting the TimeProvider
Table 6-7. Alarm Codes (Continued)
Event ID
Description
INPAIS
The specified input port has an
AIS. When detected, the input
is immediately removed as a
possible reference. The AIS
must be continuously present
for the FLTDELAY period before
disqualifying the input as a pos-
sible reference. Once set, this
alarm clears when the input sig-
nal is fault-free for the CLRDE-
LAY period.
INPLOS
The specified input port has a
LOS. When detected, the input is
immediately removed as a possi-
ble reference. The LOS must be
continuously present for the FLT-
DELAY period before disqualify-
ing the input as a possible
reference. The alarm clears
when the input signal is fault-free
for the CLRDELAY period.
INPOOF
The specified input port has an
OOF. When detected, the input
is immediately removed as a
possible reference. The OOF
must be continuously present for
the FLTDELAY period before dis-
qualifying the input as a possible
reference. The alarm clears
when the input signal is fault-free
for the CLRDELAY period.
INPFRQ
The specified input port's
calculated received frequency
exceeds the pull-in range of the
LO. This alarm disqualifies an
input as a system reference.
Once set, this alarm clears
when the input frequency is
within the defined pull-in range
limits.
INP
Specified input port has an
PHASE
excessive phase measurement
that disqualifies it.
182 TimeProvider User's Guide
AID
Service
TYPE
Affecting
T1
NSA
MN
T1
NSA
MN
T1
NSA
MN
T1
NSA
MN
T1
NSA
MN
097-58001-02 Revision G – April 2008
Alarm Level
SSU
PRR
SUB
Mode
Mode
Mode
MN
MN
MN
MN
MN
MN
MN
NR
MN