Symmetricom EDGE CLOCK 1000 User Manual page 172

Edge clock
Table of Contents

Advertisement

Chapter 6 Maintaining and Troubleshooting the TimeProvider
Troubleshooting the TimeProvider
Table 6-5. Event Codes (Continued)
Keyword
Event ID
Description
FRMTYPE
Indicates the type of
input framing or the
input frequency. Sets
the input framing type
OUTSTATE
The specified output
state has changed
RQLEVEL
The received quality
level on the specified
input has changed
CLRDELAY
Time, in seconds,
before a faulted signal
indicates it is valid as a
system reference
ELEVTIME
Indicates that Alarm
elevation time (1440
min.) is enabled or
disabled
FACTORY
Indicates that the unit
has been reset to
Factory default. All
modules installed in
the system are reset
FLTDELAY
Time, in seconds,
before faulted signal
indicates it is not valid
as a system reference
172 TimeProvider User's Guide
AID
Default Value/
TYPE
Keyword
T1
Output = 2M
T1
DISABLE
T1
n/a
SYS Events
EQPT
5 s
EQPT
DISABLE
EQPT
n/a
EQPT
10 s
Description of Values
1.544M – 1.544 MHz
2M – 2048 kHz
6.312M – 6.312 MHz
CAS – CAS Input
CCS – CCS Input
ESF – Extended SuperFrame
input
CC – Composite Clock input
ISOLATED_1 – Generates an
isolated one test pattern for
T1 outputs
JCC – Japan Composite Clock
JCC4 – Japan Composite
Clock with 400 Hz
ENABLE – The output
generates the defined signal
type
DISABLE – Disables the
output and clears all active
alarms associated with the
input
Displays the prior quality level
followed by the new quality
level
0 to 1000 s
ENABLE | DISABLE
n/a
1 to 15 s
097-58001-02 Revision G – April 2008