Galaxy Flex Installer Manual
Bell Time [51.01]
Use this option to set the bell time on activation.
The default is 15 minutes and the range is 0 to 30 minutes. Use 00 minutes to set the bell
time to infinity.
You can assign a different value to each group.
The entry/exit horn is subject to the Bell Time parameter in both the set and unset
conditions.
Bell Delay [51.02]
Use this option to delay bell activation after an alarm.
The default is 0 minutes and the range is 0 to 20 minutes.
Bell Delay is overridden by a comms failure (either a Comms Fail on the Communication
Module or by the activation of a Line Fail zone used to monitor a digicom).
You can assign a different value to each group.
Abort Time [51.03]
The abort function delays the activation of a full intruder alarm condition following an entry
alarm. This parameter has 2 sub-options:
Abort Time [51.03.1]
Range 0 to 300 seconds. You can assign a different value to each group.
The abort time is initiated:
Whenever a zone that is not on the entry route (Final, Entry and Exit zones) is
activated, for example when a user strays from the entry route.
A valid code is not entered before the entry time expires.
The standard abort operation is as follows:
For entry route deviation, the signalling of an intruder alarm is delayed.
If a valid code is entered before the entry time expires:
The intruder is not signalled.
The system does not require a system reset.
If a valid code is not entered before the entry time expires or an entry timeout condition
occurs:
The intruder is signalled at the end of the entry time.
The Abort timer starts on expiry of the entry time.
Parameters [51]
85