Galaxy Flex Installer Manual
Program Outputs [53]
51 – 55 Link A – E (Reflex)
Link outputs have no inherent function. They are designed for use with Links [54] to
provide the engineer with a means of activating a specific output address. Link outputs can
be activated by any of the link option sources. The operation of the Link output is dependent
on the Output Mode and Groups assigned to the output. The Groups assigned to the Link
must have at least one group common to the link output if that output is to be activated. This
feature can be used to multiply the number of different link outputs available on the system.
Note: When a zone function is the source of a Link output type, then a point-to-point link
is available and is as effective as direct wiring.
66 RF Jam (Latch)
This output is activated when an RF RIO detects an interference level sufficient to cause
radio jamming.
67 RF Super (Latch)
This output is activated when there is a supervision failure on a supervised RF detector.
Activation occurs when the system has received no signals (including periodic check-in
signals) from a particular detector within the programmed supervision period.
68 Bell Fail (Reflex)
This output activates when a bell fail zone causes a fault condition.
76 Fault (Latch)
This output activates any time there is a fault condition present on the panel and clears when
all the fault conditions have cleared.
The following fault types activate the fault output:
Line Fail (any module), ARC Comms Fail (any module), RF Jam, RF Low Battery, RF
Supervision Failure, Bell Fail (from a bell fail zone), AC Fail (panel, AC zone or power
supply), Battery Fail (panel, battery zone or power supply), Mask.
SMS signalling faults will not activate the fault outputs.
77 Bell Test (Pulse)
This output activates when Bell Test is selected via option 32, and causes the bell and strobe
output to activate. This output is normally used to activate a relay to cut power to the bell.
78 Comms Test (Pulse)
This output is used for remote routine inspection via the downloader software. When a
remote inspection is carried out, the output activates for 10 seconds in order to trigger the
test input of an external comms device.
81 Listen-in (Latch)
This output activates after an alarm activation when an audio transmission is in progress.
132