Diagnostics and troubleshooting
12.2 Diagnostics
12.2.4.24

Diagnostic value '30.TEMP - Current temperature'

Display range:
Purpose:
12.2.4.25

Diagnostic value '31.TMIN - Minimum temperature' / '32.TMAX - Maximum temperature'

Display range:
Purpose:
12.2.4.26
Diagnostic value '33.T1' ... '41.T9' - Number of operating hours in the temperature range
1 to 9
Display range:
Purpose:
Temperature range [°C]
Operating hours in temperature ranges T1 to T2
12.2.4.27

Diagnostic value '42.VENT1' / '43.VENT2'

'42.VENT1' Number of switching cycles of pilot valve 1
'43.VENT2' Number of switching cycles of pilot valve 2
Display range:
268
°C: -50 ... 100
°F: -58 ... 212
Current temperature in the positioner enclosure. The sensor is
present on the basic electronics. In order to switch over the temper‐
ature display between °C and °F, press the
°C: -50 ... 100
°F: -58 ... 212
The minimum and maximum temperatures within the enclosure are
constantly determined and saved as with a min/max pointer. This
value can only be reset in the factory.
In order to switch over the temperature display between °C and °F,
press the
button.
0 ... 4.29E9
Statistics about the duration of operation in different temperature
ranges is maintained in the device. An average of the measured
temperature is taken every hour and the counter assigned to the
corresponding temperature range is incremented. This helps in
drawing conclusions about the past operating conditions of the de‐
vice and the entire control valve.
The temperature ranges are classified as follows:
T1
T2
T3
-
≥ -30
≥ -15
≤ -30
< -15
< 0
0 ... 4.29E9
T4
T5
T6
≥ 0
≥ 15
≥ 30
< 15
< 30
< 45
Operating Instructions, 05/2019, A5E00127926-AC
button.
T7
T8
T9
≥ 45
≥ 60
≥ 75
< 60
< 75
-
SIPART PS2 with PROFIBUS PA