5.2.3.5
EMC filter modules 6DR4004-6F and -8F
Procedure
1. Connect the external position detection as follows.
①
Connection of terminal Vcc is only needed for 6DR4004-2ES, -3ES and -4ES.
2. If potentiometers or external signal sources are used, configure the switch blocks in
accordance with the following table:
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
1
Measuring range
Switch block 1
S1-1
6DR4004-.N/P/R
ON
(NCS)
C73451-A430-
ON
D78
6DR4004-1ES /
ON
-2ES / -3ES / -4ES
10 ... 20 kΩ
ON
5 kΩ
OFF
3 kΩ
OFF
S1-2
S2-1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
OFF
ON
5.2 Electrical wiring
Switch block 2
S2-2
S2-3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Connect
S2-4
OFF
OFF
OFF
OFF
OFF
OFF
89