Definition Of The Status - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Functions/operations using PROFIBUS PA
9.3 Cyclic data transfer
Byte
Bit
Name and meaning
2
0
DIA_MAINTENANCE_ALARM
Maintenance alarm
1
DIA_MAINTENANCE_DEMANDED
Maintenance demand
2
DIA_FUNCTION_CHECK
Function check
3
DIA_INV_PRO_COND
Invalid process conditions
4
Reserved
... 7
3
0
Reserved
... 6
7
EXTENSION_AVAILABLE
Extension available
9.3.3.3

Definition of the status

Status byte
The status is used to provide information about the quality of the input and output values. This
information is classified into four stages. Quality stages such as "Bad", "Uncertain", "Good" and
"Good (cascade)" are accompanied with further information. In this case, it deals with the sub-
status and the limit bits. The status byte has the following structure:
Quality
Limit bits
226
7
6
Quality
Cause
To determine the cause, check in
DIAGNOSIS_EXTENSION and
DIAGNOSIS_EXTENSION_2
which diagnosis event has trig‐
gered the message.
To determine the cause, check in
DIAGNOSIS_EXTENSION and
DIAGNOSIS_EXTENSION_2
which diagnosis event has trig‐
gered the message.
The device is in on-site operation
or the FEEDBACK_VALUE is si‐
mulated
To determine the cause, check in
DIAGNOSIS_EXTENSION and
DIAGNOSIS_EXTENSION_2
which diagnosis event has trig‐
gered the message.
-
-
Further information about the trig‐
gering diagnosis event is availa‐
ble in DIAGNOSIS_EXTENSION
and DIAGNOSIS_EXTEN‐
SION_2.
Status byte structure
5
4
Sub-status
00
Bad
01
Uncertain
10
Good
11
Good (cascade)
00
Good
Measures
Depends on the
triggering diagnos‐
tics event.
Depends on the
triggering diagnos‐
tics event.
-
Depends on the
triggering diagnos‐
tics event.
-
-
-
3
2
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
Group
M
M12, M
F
P
-
-
-
1
0
Limit bits