Automatic Initialization Of Part-Turn Actuators - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Commissioning
7.7 Commissioning part-turn actuators
7.7.2

Automatic initialization of part-turn actuators

Condition
The following conditions must be fulfilled before activating the automatic initialization:
1. The travel range of the actuator can be passed through completely.
2. The actuator shaft is at a central position.
Initializing the part-turn actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, press the
until the display shows the following:
2. Use the
the following:
3. Call the "2.YAGL" parameter. To do this, briefly press the
already been set to 90° automatically. The display shows the following:
4. Call the "4.INITA" parameter. To do this, briefly press the
following:
126
button to change from linear actuator to part-turn actuator until the display shows
button for at least 5 seconds
button. This parameter has
button. The display shows the
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
. The settings

Advertisement

Table of Contents
loading

Table of Contents