Siemens SIPART PS2 Operating Instructions Manual page 121

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of parameter
3 is optional. The display shows the determined total stroke only at the end of the
initialization phase.
– Press the
– Call the "3.YWAY" parameter. To do this, press
5. Call the "4.INITA" parameter. To do this, briefly press the
following:
6. Start the initialization process. To do this, keep the
until the display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN 1" to "RUN 5" are shown in the lower
line on the display. The initialization process depends on the actuator used, and takes up to
15 minutes.
7. The following display indicates that the automatic initialization is complete:
See also
Sequence of automatic initialization (Page 111)
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
button if you do not require any information about the total stroke in mm.
You are then directed to parameter 4.
Note
Set the "3.YWAY" parameter
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter with the buttons
7.6 Commissioning linear actuators
. The display shows the following:
and
to the read value.
button. The display shows the
button pressed for at least 5 seconds
Commissioning
121

Advertisement

Table of Contents
loading