Parameter assignment
8.3 Description of parameters
P2.STATE - Status of monitoring position average value
Possible settings:
Purpose:
Factory setting:
Note
Current average value of position
The respective current average value of position is displayed in the Diagnostic value '20.PAVG
- Average value of position' (Page 265). If no average value of position has been calculated,
'COMP' is displayed as the diagnostic value.
P3.LEVL1 - threshold 1
Possible settings:
Purpose:
Factory setting:
186
IdLE / rEF / ###.# / Strt
Use this sub-parameter to start the calculation for average value of
position. If an average value of reference has never been deter‐
mined, the parameter value is 'IdLE'.
Then start the calculation by pressing the
The value in the display changes from 'IdLE' to 'rEF'. The average
value of reference is calculated.
When the time interval expires, the calculated average value of
reference is shown on the display.
IdLE
0.1 ... 100.0
Use this sub-parameter to set threshold 1 for the maximum devia‐
tion of the current average value of position from the average value
of reference. The value is given in percent. Set the threshold in a
range from '0.1' to '100.0'.
The positioner triggers the threshold 1 message if the difference
between the average value of position and the average value of
reference exceeds threshold 1. This message is only output if
threshold 2 or 3 is not exceeded at the same time. The process to
activate and display this message is described in the 'XDIAG' pa‐
rameter.
2.0
button for 5 seconds.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC