Siemens SIPART PS2 Operating Instructions Manual page 258

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Diagnostics and troubleshooting
12.2 Diagnostics
No.
Short de‐
Meaning
scription
15
DEVI
Dynamic control valve behavior
16
ONLK
Pneumatic leakage
17
STIC
Stiction (slipstick)
18
ZERO
Lower endstop
19
OPEN
Upper endstop
20
PAVG
Average value of position
21
P0
Potentiometer value of lower endstop (0%)
22
P100
Potentiometer value of upper endstop (100%)
23
IMPUP
Pulse length up
24
IMPDN
Pulse length down
25
PAUTP
Pulse pause
26
DBUP
Deadband up
27
DBDN
Deadband down
28
SSUP
Slow step zone up
29
SSDN
Slow step zone down
30
TEMP
Current temperature
31
TMIN
Minimum temperature (min/max pointer)
32
TMAX
Maximum temperature (min/max pointer)
33
T1
Number of operating hours in temperature range 1
34
T2
Number of operating hours in temperature range 2
35
T3
Number of operating hours in temperature range 3
36
T4
Number of operating hours in temperature range 4
37
T5
Number of operating hours in temperature range 5
38
T6
Number of operating hours in temperature range 6
39
T7
Number of operating hours in temperature range 7
40
T8
Number of operating hours in temperature range 8
41
T9
Number of operating hours in temperature range 9
42
VENT1
Number of switching cycles of pilot valve 1
43
VENT2
Number of switching cycles of pilot valve 2
44
VEN1R
Number of switching cycles of pilot valve 1, resettable 0 ... 4.29E9
45
VEN2R
Number of switching cycles of pilot valve 2, resettable 0 ... 4.29E9
46
STORE
Save the current values as 'last maintenance'
(press
47
PRUP
Prediction up
48
PRDN
Prediction down
49
WT00
Number of operating hours in the travel range WT00
258
button for 5 seconds)
Representable di‐
Unit
agnostics values
0.0 ... 100.0
%
0.0 ... 100.0
-
0.0 ... 100.0
%
0.0 ... 100.0
%
0.0 ... 100.0
%
OFF, IdLE, rEF,
%
COMP
0.0 ... 100.0
0.0 ... 100.0
%
0.0 ... 100.0
%
6 ... 160
ms
6 ... 160
ms
2 ... 28 ... 320
ms
0.1 ... 10.0
%
0.1 ... 10.0
%
0.1 ... 10.0 ...
%
100.0
0.1 ... 10.0 ...
%
100.0
-50 ... 100
°C
-58 ... 212
°F
-50 ... 100
°C
-58 ... 212
°F
-50 ... 100
°C
-58 ... 212
°F
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
-
0 ... 4.29E9
-
-
-
-
-
1 ... 40
-
1 ... 40
-
0 ... 4.29E9
Hours
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
Properties

Advertisement

Table of Contents
loading

Table of Contents