Collective diagnostics messages
Collective diagnostics messages in the case of the activated condensed status are shown in
the following table:
Byte
Bit
Name and meaning
0
0
Reserved
... 7
1
0
Reserved
... 2
3
DIA_WARMSTART
Warm restart executed (goes to "0" after
10 s)
4
DIA_COLDSTART
Restart executed
(goes to "0" after 10 s)
5
DIA_MAINTENANCE
Maintenance required
6
Reserved
7
IDENT_NUMBER_VIOLATION
Identification number changed
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
Functions/operations using PROFIBUS PA
Cause
-
-
To determine the cause, check in
DIAGNOSIS_EXTENSION and
DIAGNOSIS_EXTENSION_2
which diagnosis event has trig‐
gered the message.
-
You have changed the PROFI‐
BUS identification number pa‐
rameter during the active cyclic
operation. The device reports the
identification number violation
and displays a failure warning. In
case of a restart, the device will
no longer participate in cyclic
user data exchange unless the
system configuration is changed.
-
To determine the cause, check in
DIAGNOSIS_EXTENSION and
DIAGNOSIS_EXTENSION_2
which diagnosis event has trig‐
gered the message.
9.3 Cyclic data transfer
Measures
Group
-
-
-
-
Check the wiring
-
and the supply volt‐
age.
-
-
Depends on the
M1, M12,
triggering diagnos‐
M
tics event.
-
-
Modify the configu‐
-
ration data
(change the GSD)
such that it is con‐
sistent with the
identification num‐
ber set in the de‐
vice.