Siemens SIPART PS2 Operating Instructions Manual page 124

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Commissioning
7.6 Commissioning linear actuators
9. Press the
following:
Note
Fault message "RANGE"
The selected end position is beyond the permissible measuring range if the "RANGE"
message is output on the display. Correct the settings as follows:
1. Move the friction clutch until the display shows "OK".
2. Press the
3. Move the actuator to another position using the
4. Abort the manual initialization process by pressing the
5. Then return to "P manual mode".
6. Correct the actuator travel and the position detection.
10.Determine the upper endstop of the actuator spindle. Move the actuator to the desired
position using the
11.Press the
Note
Fault message "Set Middl"
The lever arm is not in the horizontal position if the "Set Middl" message is output on the
display. To correct the fault, set the reference point of the sine correction. Proceed as
follows:
1. Move the lever arm to the horizontal position using the
2. Press the
12.The initialization process is automatically resumed. Initialization steps "RUN 1" to "RUN 5"
are output in the bottom line of the display. The following is displayed when the initialization
has been completed successfully:
Note
Total stroke
If the "3.YWAY" parameter has been set, the display shows the total stroke in mm.
124
button. The current position of the actuator is applied. The display shows the
button.
or
button.
button. The current position of the actuator is applied.
button.
or
button.
button.
or
button.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC

Advertisement

Table of Contents
loading

Table of Contents