Terms And Definitions; Safety Instrumented System (Sis) Certification - Emerson 5301HxxxxxxxxxxxxxxZZ Series Reference Manual

Guided wave radar level transmitter
Table of Contents

Advertisement

Safety Instrumented Systems (4-20 mA only)
April 2019
8.2

Terms and definitions

Table 8-1: Terms and Definitions
Term
DU
FIT
FMEDA
®
HART
HFT
PFD
AVG
SFF
SIF
SIL
SIS
Safety Response Time
Type B device
8.3

Safety Instrumented System (SIS) certification

For safety instrumented systems usage, the 4-20 mA analog output is used as the primary
safety variable. It is configured to activate the alarm function if an error occurs. If a
measured value goes beyond the measurement range, the transmitter enters saturation
mode (limit alarm is disabled) or alarm mode, depending on the current configuration.
The minimum time for the alarm condition is 200 ms.
The measurement signal used by the logic solver must be the analog 4-20 mA signal
proportional to the level generated. The HART protocol can only be used for setup,
calibration, and diagnostic purposes, not for safety critical operation.
The Rosemount 5300 Level Transmitter is IEC 61508 certified accordingly:
Low and high demand: Type B element
SIL 2 for random integrity @ HFT=0
SIL 3 for random integrity @ HFT=1
SIL 3 for systematic capability
246
Definition
Dangerous Undetected
Failure In Time per billion hours
Failure Modes, Effects and Diagnostic Analysis
Highway Addressable Remote Transducer
Hardware Fault Tolerance
Average Probability of Failure on Demand
Safe Failure Fraction
Safety Instrumented Function
Safety Integrity Level – a discrete level (one out of four) for
specifying the safety integrity requirements of the safety
instrumented functions to be allocated to the safety
instrumented systems. SIL 4 has the highest level of safety
integrity, and SIL 1 has the lowest level.
Safety Instrumented System – an instrumented system
used to implement one or more safety instrumented
functions. An SIS is composed of any combination of
sensors, logic solvers, and final elements.
The delay between a change in the measured process and
the indication of that change at the safety-rated output.
Complex device using controllers or programmable logic,
as defined by the standard IEC 61508.
Reference Manual
00809-0100-4530
Rosemount 5300 Level Transmitter