Diagnostic messages

7.2.1
Device status
Device status messages that may appear on the Integral Display, on the handheld
communicator, or in Rosemount Radar Master are shown in
Table 7-1: Device status
Message
Running Boot Software
Device Warning
Device Error
Sim Mode 0 Active
Advanced Simulation Mode
Active
Interface Invalid
Invalid Measurement
User Register Area Write
Protected
Write Protected Jumper Set
Factory Settings Used
Probe missing
7.2.2
Errors
Error messages that may be displayed on the Integral Display, on a handheld
communicator, in AMS Device Manager, or in Rosemount Radar Master are shown in
7-2. Errors normally result in Analog Output alarm.
Errors are indicated in Rosemount Radar Master in the Diagnostics window.
Reference Manual
Description
The application software could not be
started.
A device warning is active.
A device error is active.
The simulation mode is active.
The advanced simulation mode is active.
The interface measurement is invalid.
The level measurement is invalid.
The configuration registers are write
protected.
Write protection jumper on the display is
enabled.
The factory default configuration is used.
Probe is not detected.
Service and troubleshooting
Table
7-1:
Action
Contact Emerson Service Department.
See Warning Messages for details.
See Error Messages for details.
Turn off the simulation mode in
Rosemount Radar Master, select Tools,
Simulation Mode, and click the Stop
button.
To turn off the Advanced Simulation
mode, set Holding Register 3600=0 (see
View/edit holding
registers).
Check the Error Messages, Warning
Messages, and the Interface Status for
details.
Check Error Messages, Warning
Messages, and Measurement Status for
details.
Use the Lock/Unlock function to turn off
the write protection (see
Write
protection).
Remove the write protection jumper.
The transmitter has lost its calibration.
Contact Emerson Service Department.
Check that the probe is correctly
mounted. Check the connection between
probe and transmitter head.
April 2019
Table
171