Safety-certified identification

All Rosemount 5300 Level Transmitter must be identified as safety-certified before
installing into SIS systems.
Transmitter that have been considered for the hardware assessment, to which this section
applies.
Models with the QS option code are supplied with a manufacturer's prior use certificate
of FMEDA data.
Models with the QT option code are IEC 61508 certified by an accredited 3
agency for use in safety instrumented systems up to SIL 3. (For single use (1oo1)
capable up to SIL 2 and for redundant use (1oo2 or 2oo3) capable up to SIL 3.)
Table 8-2: Rosemount 5300 Series Safety-Certified Option Model Codes
Rosemount 5300 4-20 mA HART Guided Wave Radar Level and Interface Transmitter
Hardware
Software/Firmware
8.4.1
Identify a safety-certified transmitter
To identify a Rosemount 5300 Level Transmitter safety-certified transmitter:
Procedure
1. Verify the option code QS or QT in the model code, on the label affixed to the
2. Check if a yellow label is affixed to the transmitter head for option code QT.
3. Before doing any configuration, write down the serial number from the label, and
Reference Manual
Table 8-2
outside of the transmitter head.
make sure you are connected to the correct transmitter by verifying the same serial
number in your communication device.
Note
In Rosemount Radar Master, this information can be found in the Device Properties
window. Select Device → Properties.
Safety Instrumented Systems (4-20 mA only)
lists the versions of the Rosemount 5300 Level
Model 5301HxxxxxxxxxxxxxxZZ
Model 5302HxxxxxxxxxxxxxxZZ
Model 5303HxxxxxxxxxxxxxxZZ
Note
Transmitters will be marked with "QS" or "QT"
at the end of the model number in place of ZZ
above.
2.A1 or higher
April 2019
rd
party
247