Specifications and reference data
A.1
Performance specifications
A.1.1
General
Reference conditions
Single Standard probe, 77 °F (25 °C) in water (DC=80) and ambient pressure in a 4-in. pipe
using Trim Near Zone function.
Reference accuracy
± 0.12 in. (3 mm) or 0.03% of measured distance, whichever is greatest
For probes with spacers, the accuracy may deviate close to the spacers. Accuracy may be
affected by remote housing.
Repeatability
± 0.04 in. (1 mm)
Ambient temperature effect
± 0.008 in. (0.2 mm) /°K or ± 30 ppm/°K of measured value, whichever is greatest
Electromagnetic interference effect
•
Shielded cable: ± 0.2 in. (5 mm)
•
Unshielded cable: ± 2 in. (50 mm)
For F
OUNDATION
power supply and transmitter to achieve optimum performance.
Thresholds may need to be adjusted, see
for general guidelines on manual threshold settings.
Update interval
Minimum 1 update per second
A.1.2
Environment
Vibration resistance
•
Aluminum housing: Level 1 IEC 60770-1/IEC 61298-3 ed 1 chapter 7
(10)
For the BR5 option code with ambient temperatures between -67 °F (-55 °C) and -40 °F (-40 °C), the ambient temperature
effect is ± 0.012 in. (0.3 mm) /°K or ± 45 ppm/°K of measured value, whichever is greatest.
(11)
Deviation through electromagnetic interference according to EN 61326.
Reference Manual
(11)
(11)
™
Fieldbus units it may be required to ground the signal cable shield at the
Specifications and reference data
Guidelines for setting the amplitude thresholds
April 2019