Troubleshooting On The Protocol Setting Data Reading/Writing; The "Err." Led Is Lit - Mitsubishi Melsec-L Series User Manual

Communication module
Hide thumbs Also See for Melsec-L Series:
Table of Contents

Advertisement

15.3.22 Troubleshooting on the protocol setting data reading/writing

Symptom
• The user-edited protocol setting in the
• The "ERR." LED turns on
when protocol setting
data are written to the
C24.

15.3.23 The "ERR." LED is lit

Symptom
• A communication error has occurred.
• Switch settings of the C24 are incorrect. • Review the switch settings of the C24.
• The communication protocol mode is set
• "ERR." LED is lit
• The C24 is powered off while data are
15 - 54
Cause
predefined protocol support function of
GX Works2 has an error.
Or, function data not supported by the
C24 are included in the protocol setting
data.
Cause
to "Predefined protocol mode", and
linked operation is set for two interfaces.
written to the flash ROM.
Corrective action
• In Protocol setting data error information
(buffer memory: 4086
to 4089
H
the error part (protocol No, packet No, or
element No.) and correct it. Check the
protocol setting for an error paying
attention to the following, and write
corrected data to the C24 again.
(1) When an error was detected in the
user-edited protocol
Check if the following condition for
element placement are satisfied in the
packet setting or not:
If any elements of 1) and 2) are in the
same packet, 1) must be placed before
2).
1)• Conversion variable (fixed number
of data, fixed number of digits (1 to
10), no signed character)
• Conversion variable (fixed number
of data, fixed number of digits (1 to
10), variable decimal point)
• Conversion variable (fixed number
of data, variable number of digits,
number of data is 1, delimiter set)
2)• Non-conversion variable (variable
length)
• Conversion variable (variable
number of data)
• Conversion variable (fixed number
of data, variable number of digits,
number of data is 1, no delimiter)
• Conversion variable (fixed number
of data, variable number of digits,
number of data is 2 or more)
• Non-verified reception (variable
number of characters)
(2) When function data not supported by
the C24 are included in the protocol
setting data
Check the version of the C24 to
confirm supported functions.
Set the protocol within the range of
supported functions if any unsupported
function is applied.
Corrective action
• Check the error and remove the cause
according to Section 15.2.
• For communication in the predefined
protocol mode, change the setting to
separate operations.
• Write the data to the flash ROM again.
15 TROUBLESHOOTING
Non-
Bidirectional
MC
procedural
protocol
), locate
H
Non-
Bidirectional
MC
procedural
protocol
Predefined
protocol
Predefined
protocol
15 - 54

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lj71c24Lj71c24-r2