Mitsubishi Melsec-L Series User Manual page 72

Communication module
Hide thumbs Also See for Melsec-L Series:
Table of Contents

Advertisement

6 - 27
Item
When the "Current Value" is 1 (ON)
Error in the CPU module.
Insufficient power supply capacity.
Module is not connected correctly.
CH
C/N
Error in the cable, CPU module, or
the C24.
CH1: CH1 side communication error
CH
ERR.
CH2: CH2 side communication error
6 SETTING AND WIRING
Corrective action
Remove errors in the CPU module.
Examine the power supply capacity.
Reinstall the module properly.
Check each module and remove the
cause of the error.
Reconnect the cable correctly.
Reinstall the module properly.
Reconnect the cable correctly.
Examine the test wiring connection.
6 - 27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lj71c24Lj71c24-r2

Table of Contents