5. PROGRAMMING
_ _ _ _ _ _ _ _ _ _----.lIMELSEC;4
5.2
Writing the Initial Data
Note the following when writing the initial data to the master
module buffer memory.
The initial data includes the number of remote I/O stations
(address 0), number of retries (address 1), and partial refresh
station (addresses 250 to 282).
The partial refresh stations must be defined only when partial
refresh type remote I/O stations are used. For information on
setting, see Section 5.4.2.
(1) Buffer memory assignment related to initial data
Address (Decimal)
o
Number of remote 110 stations
1
Number of retries
(2) Number of remote I/O stations (address 0)
(a) Define the remote I/O station range for I/O refresh.
(b) I/O refresh is performed for up to the remote I/O station
specified in address O.
For example, remote I/O stations 1 to 20 are refreshed
when 20 is set to address O.
(c) Specify the last remote I/O station number connected to
the master module.
The value specified should include the number of occupied
stations if the last remote I/O station occupies two or more
stations, e.g. set 13 to address 0 to allow data link for up to
station 10 that occupies 4 stations.
(d) Defaults to O.
(e) Any value between 1 and 64 may be specified. Any value
set outside this range flags an initial data error when Y18 is
switched on.
(3) Number of retries (address 1)
(a) Define the number of retries made to the faulty remote I/O
station.
(b) Defaults to 2.
(c) Any value between 0 and 32 may be specified.
(d) A communication error occurs if the faulty remote I/O
station cannot be restored after retry is made the specified
number of times.
(4) Initial data write timing
The initial data should be written when Y18 is off because the
I
values on the leading edge of Y18 are valid.
(5) Program example
The following program sets the number of remote I/O stations
to 20 and the number of retries to 3.
ae
l
Pulses the initial data write command.
De
Sets 20 (number of remote 110 stations area) to DO.
01
Sets 3 (number of retries) to D1.
K
Writes the initial data to master module buffer
2
memory.
ee
CNOlJ
- - - - - - - - - - - - - < C N O U
I
- - - - - - - { n o
~'iHl0
Initial data
F ".
~
rite command
,
I f - - - - - - - - - - - - - { C P L S
'~l
~
5-2
IB (NAJ 66164·A