HEIDENHAIN iTNC 530 Service Manual page 181

Hide thumbs Also See for iTNC 530:
Table of Contents

Advertisement

Pinging from the control to the laptop (test of the connection):
Meaning of the
LEDs on the
LED
Ethernet data
interface X26
Green
Yellow
After having finished data back-up and separated the connection, do not forget to restore the
Restoring original
original network settings of your laptop or of the iTNC 530!
settings
On the laptop:
On the control:
Up to NC software 340 49x-04:
As of NC software 34049x-05:
July 2010
Enter the code number NET123, confirm with ENTER and subsequently press the PING soft
key.
Enter the IP address of the laptop.
Confirm ENTER. -->If the connection functions, you receive the answer HOST RESPOND. If the
connection does not function, the TIMEOUT message is displayed.
Note
If the "pinging" does not function, you have to check again all settings and the hardware
(Ethernet cables, Ethernet cards).
If pinging from control to laptop does not work, an active firewall on the laptop may be the
reason.
Condition
Blinking
Off
On
Off
Activate the original settings with the "General" button on the laptop with Windows XP or enter
the original setting noted down and press ENTER to confirm.
Place the cursor in the line with the original network settings and press the ACTIVATE LINE
soft key.
If you have overwritten the original settings on the control, you have to enter them again or
copy the back-up file (e.g., ip4n00.a) to file ip4.n00.
Press the END key twice. --> The control reboots and transfers the new settings.
Note
You can / should protect the file ip4.n00 with the original network settings.
Enter PLC code number --> Call program manangement --> Place the cursor in the NET
folder on file ip4.n00 --> Switch to the next soft-key row --> Press MORE FUNCTIONS soft
key --> Set the locking --> P (Protected) appears in the status column.
Place the cursor in the line with the original network settings and press the ACTIVATE LINE
soft key.
If you have overwritten the original settings on the control, you have to enter them again or
copy the back-up file (e.g., ip4n00.a) to file ip4.n00.
Press the END key twice. --> The control reboots and transfers the new settings.
Meaning
Interface active
Interface inactive
100 Mbit network
10 Mbit network
13 – 181