Mounting - Siemens SINAMICS S110 Manual

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Motor reactors 6SE6400-3TC14-5FD0 for PM240-2, FSE
Figure 6-6
6.1.4

Mounting

The motor reactors for Power Modules PM240-2, frame sizes FSA to FSE, are dimensioned
for installation in cabinets. The motor reactor is installed on the mounting surface next to the
Power Module.
Table 6- 1
Frame size
FSA
FSB
FSC
FSD
FSE
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
PE terminal M8 x 16
Dimension drawing motor reactors for PM240-2, FSE, all data in mm and (inch)
Mounting of motor reactors for PM240-2 Power Modules
Fastening
4 x M4 screws
4 x M4 nuts
4 x M4 washers
4 x M5 screws
4 x M5 nuts
4 x M5 washers
4 x M6 screws
4 x M6 nuts
4 x M6 washers
4 x M8 screws
4 x M8 nuts
4 x M8 washers
Power components on the motor side
6.1 Motor reactors
Tightening torque
3 Nm
5 Nm
8 Nm
10 Nm
125