10.7
Notes on electrical cabinet cooling
10.7.1
General information
Cabinets can be cooled in a number of ways including the following:
● Filtered fans
● Heat exchanger
● Cooling unit
The decision in favor of one of these methods will depend on the prevailing ambient
conditions and the cooling power required.
The air routing within the cabinet and the ventilation clearances specified here must be
ensured. Other components or cables must not be installed in these areas.
You must comply with the following specifications when installing SINAMICS components:
● Ventilation clearance
● Cable routing
● Air guidance, air-conditioner
Table 10- 7
Ventilation clearances around the components
Component
CU305 PN
CU305 DP
CU305 CAN
SMCxx
Line filter
Line reactor
PM240-2 Blocksize, frame size FSA ... FSC
PM240-2 Blocksize, frame size FSD ... FSE
Motor reactor
Braking resistor (vertical installation)
Braking resistor (horizontal installation)
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
Cabinet design and EMC for components, Blocksize format
Clearance above and below in mm
und (inch)
50 (1.97)
50 (1.97)
50 (1.97)
50 (1.97)
100 (3.94)
100 (3.94)
Above: 80 (3.15)
Below: 100 (3.94)
Above: 300 (11.81)
Below: 350 (13.78)
100 (3.94)
Above: 1000 (39.37)
Above: 1000 (39.37)
10.7 Notes on electrical cabinet cooling
Clearance in front of the compo-
nent in mm und (inch)
0
0
0
0
0
0
0
100 (3.94)
0
All around: 100 (3.94)
All around: 250 (9.84)
239