Risk of burns resulting from high surface temperatures of the line reactors
The surface temperature of the line reactors may exceed 80° C. Contact with the surface
can cause you to suffer severe burn injuries.
• Mount the line reactor so that it cannot be touched. If this is not possible, at the
NOTICE
Damage to the system due to impermissible line reactors
An impermissible line reactor may cause damage to the system and any further loads
operated on the same power network.
• Only use line reactors that Siemens has authorized for SINAMICS.
NOTICE
Line reactor damage due to interchanged connections
Interchanging the input and output connections will damage the line reactor.
• Connect the incoming power supply cable to 1L1, 1L2, 1L3.
• Connect the outgoing cable to the load at 2L1, 2L2, 2L3.
Note
Malfunctions through magnetic fields
Reactors produce magnetic fields that can disturb or damage components and cables.
• Arrange the components and cables at a suitable distance (at least 200 mm) or shield the
magnetic fields appropriately.
Note
Connection cables
• Keep the connecting cables to the Power Module short (max. 5 m.)
• Use shielded connection cables.