CU305 Control Units
7.3 Interface description
Note
Function equipotential bonding for distributed DRIVE-CLiQ nodes
Integrate all of the components that are connected via DRIVE-CLiQ into the function
equipotential bonding concept. The connection should be preferably established by mounting
on metallic bright machine and plant components that are connected with one another using
an equipotential bonding conductor.
Alternatively, you can establish equipotential bonding using a conductor (min. 6 mm²), which
as far as possible, is routed parallel to the DRIVE-CLiQ cable.
This applies to all distributed DRIVE-CLiQ nodes such as DME20, SME2x, SME12x, etc.
7.3
Interface description
7.3.1
General interface overview
Table 7- 2
Terminal
Specific interfaces
X150 P1 / X150 P2
X126
Identical interfaces
X100
X124
X130
X131
X132
X133
X23
X22
X520 / X521 / X522
132
Interface overview classified according to terminal
CU305 PN
PROFINET
-
DRIVE-CLiQ
Electronics power supply
Fail-safe digital inputs
Fail-safe digital inputs/outputs
Digital inputs/outputs, analog input
Digital inputs, temperature sensor input
Encoder interface (HTL/TTL/SSI)
Serial interface (RS232)
Measuring sockets
CU305 DP
CU305 CAN
-
PROFIBUS
Manual, 07/2015, 6SL3097-4AC10-0BP5
-
CAN
SINAMICS S110