DC link components

5.1

DC link fuses

The Power Modules PM240-2 FSD and FSE do not have integrated overcurrent protection
for the DC link. You must therefore use aR characteristics fuses.
Line voltage 3-phase 380 ... 480 V AC
Table 5- 1
Fuses for Power Modules PM240-2 FSD
Article No.
without integrated line filter
with internal line filter
Fuses
NH IEC 60947
Rated current
Table 5- 2
Fuses for Power Modules PM240-2 FSE
Article No.
without integrated line filter
with internal line filter
Fuses
NH IEC 60947
Rated current
5.2

Braking resistors

5.2.1

Description

The PM240-2 Power Modules cannot feed back regenerated energy into the line supply. For
regenerative operation, e.g. the braking of a rotating mass, a braking resistor must be
connected to convert the resulting energy into heat.
A thermostatic switch monitors the braking resistor for overtemperature and issues a signal
on an isolated contact if the limit value is exceeded.
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
6SL3210–
6SL3210–
1PE23-8UL0
1PE24-5UL0
1PE23-8AL0
1PE24-5AL0
3NE3221
3NE3221
A
100
100
6SL3210–
1PE28-8UL0
1PE28-8AL0
3NE3224
A
160
6SL3210–
6SL3210–
1PE26-0UL0
1PE27-5UL0
1PE26-0AL0
1PE27-5AL0
3NE3222
3NE3222
125
125
6SL3210–
1PE31-1UL0
1PE31-1AL0
3NE3225
200
5
109