Motor Protection

Motor Overload Detection

The VS-606V7 protects against motor overload with a built-in electonic
thermal overload relay.
Motor Rated Current (Electronic Thermal Reference Current,
n036)
Set the rated current value shown on the motor nameplate.
Note: Setting n036 to 0.0 A disables the motor overload protective function.
Motor Overload Protection Selection (n037, n038)
n037
Setting
0
For general-purpose motor
1
For Inverter motor
2
Electronic thermal overload protection not provided.
Constant
No.
n038
Electronic Thermal
Motor Protection
Time Constant Set-
ting
The electronic thermal overload function monitors the motor tempera-
ture based on Inverter output current and time to protect the motor from
overheating. When the electronic thermal overload relay is enabled, an
error occurs, and the Inverter output is turned OFF to prevent
excessive overheating in the motor. When operating with one Inverter
connected to one motor, an external thermal relay is not needed. When
operating more than one motor with one Inverter, install a thermal relay
on each motor.
General-purpose Motors and Inverter Motors
Induction motors are classified as general-purpose motors or Inverter
motors based on their cooling capabilities. The motor overload function
operates differently for these two motor types.
Electronic Thermal Characteristics
Name
Unit
1 min 1 to 60 min
6. Programming Features
Setting Range
Factory
Setting
8 min
107