Conversion Completion Flag (Un\G10) - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.4
Conversion state can be checked for each channel.
(1) Data storage
(2) How to clear stored data
3
- 40
3.4 Buffer Memory

3.4.4 Conversion completion flag (Un\G10)

Conversion completion flag (Un\G10)
(a) The bit of the corresponding channel in Conversion completion flag turns on
(changes to "1") when conversion of conversion-enabled channels is completed.
b15 b14 b13 b12 b11 b10
0
0
0
0
Data for b8 to b15 are fixed to "0".
Figure 3.22 Storage of Conversion completion flag (Un\G10)
(b) Conversion completion flag (XE) turns on when conversion of all conversion-
enabled channels is completed.
When Operating condition setting request (Y)) is turned on, the bit of all channels in
the Conversion completion flag returns to default value ("0").
POINT
Use this area or Conversion completion flag (XE) as an interlock to read out the
measured temperature value.
b9
b8
b7
0
0
0
0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
b6
b5
b4
b3
b2
0: During conversion or unused
1: Conversion completed
b1
b0