SPECIFICATIONS
3.4.25
Conversion setting for disconnection detection (Un\G164,
Un\G165) (Q68TD-G-H02 only)
When disconnection is detected, a value stored into CH
(Un\G11toUn\G18) is set. (Refer to Section 3.2.2)
The value to be stored is selected from "Up scale", "Down scale" or "Given value".

(1) Setting methods

(a) Set the value to be stored into buffer memory.
Un\G164 (Conversion setting for
disconnection detection CH1-4)
Un\G165 (Conversion setting for
disconnection detection CH5-8)
Figure 3.38 Setting of Conversion setting for disconnection detection (Un\G164, Un\G165)
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to "Down scale" (1111
POINT

3.4.25 Conversion setting for disconnection detection (Un\G164, Un\G165) (Q68TD-G-H02 only)

to
b15
b12 b11
CH4
CH8
The value to be stored into CH
changes as follows, depending on the setting value.
1) Up scale (0
)
H
Up-scale of the range currently set is stored.
2) Down scale (1
)
H
Down-scale of the range currently set is stored.
3) Given value (2
)
H
The value set in CH
(Un\G166toUn\G173) is stored.
If a value out of the setting range is set, the module operates with the default
setting, "Down scale"(1
).
H
Measured temperature value
to
b8 b7
CH3
CH2
CH7
CH6
Measured temperature value at the
time of disconnection detection
Up scale
Down scale
Given value
Measured temperature value (Un\G11toUn\G18)
Conversion setting value for disconnection detection
).
H
3.4 Buffer Memory
to
to
b4 b3
CH1
CH5
Setting
value
0
H
1
H
2
H
3
- 59
1
2
b0
3
4
5
6
7
8