Ch[ ] Measured Temperature Value (Un\G11 To Un\G18) - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.5

CH[ ] Measured temperature value (Un\G11 to Un\G18)

"Thermal electromotive force values" input from thermocouples are converted into
"temperature values" to check values of detected temperature.
(1) Data storage
The measured temperature value rounded off to one decimal place is multiplied by 10
and the result is stored into buffer memory in 16-bit signed binary. (Drop the second
decimal place and later.)
[Setting example 1]
When the measured temperature value is 123.025
b15 b14 b13 b12 b11 b10
Figure 3.23 Storage example 1 of CH
When the measured temperature value is -123.0
b15 b14 b13
Figure 3.24 Storage example 2 of CH
POINT
0
0
0
0
0
1
Measured temperature value (Un\G11 to Un\G18)
b12 b11 b10
1
1
1
1
1
0
Measured temperature value (Un\G11 to Un\G18)
(1) When disconnection is detected or checked with a monitor, the values set in
Conversion setting for disconnection detection (Un\G164, Un\G165) or
Disconnection state conversion setting (Un\G164, Un\G165) are stored into
the CH
Measured temperature value (Un\G11 to Un\G18). (Refer to Section
3.4.25, Section 3.4.26)
(2) After the disconnection recovery, normal measured temperature value is
automatically stored.
(3) Use Conversion completion flag (XE) or Conversion completion flag (Un\G10)
as an interlock to read out the measured temperature value.
3.4.5 CH[ ] Measured temperature value (Un\G11 to Un\G18)
b9
b8
b7
b6
b5
b4
0
0
1
1
0
0
b9
b8
b7
b6
b5
b4
1
1
0
0
1
1
3.4 Buffer Memory
1230 is stored.
b3
b2
b1
b0
1
1
1
0
-1230 is stored.
b3
b2
b1
b0
0
0
1
0
3
- 41
1
2
3
4
5
6
7
8