Disconnection State Conversion Setting Function (Q68Td-G-H01 Only) - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.2.3
This disconnection state conversion setting function stores specific values into measured
temperature values when disconnection is checked.
This function can identify the disconnection detection from measured temperature values.
This function is only available for channels enable temperature conversion.
(1) Overview of disconnection monitor
3
- 14
3.2 Function List

3.2.3 Disconnection state conversion setting function (Q68TD-G-H01 only)

Disconnection state conversion setting function (Q68TD-G-H01
only)
Disconnection state
monitor signal (XC)
Disconnection state monitor
flag (Un\G49)
CH
Measured temperature value
(Un\G11 to Un\G18)
Error clear request (YF)
Figure 3.7 Overview of disconnection monitor
(a) It takes up to 11s from when line is disconnected till when disconnection is
monitored.
The measured temperature value decreases till when disconnection state is
checked.
When disconnection is checked, Disconnection state monitor flag (Un\G49) and
Disconnection state monitor signal (XC) turn on. Consequently, "ALM" LED blinks.
(b) When disconnection is checked, the value selected from "Up scale", "Down scale"
or "Given value" in Disconnection state conversion setting (Un\G164,Un\G165) is
stored into the CH
The values specified in Disconnection state conversion setting
(Un\G164,Un\G165) remains from when disconnection state is restored till when
normal measured temperature value is stored.
(c) After disconnection state is restored, the batch-update of measured temperature
value restarts automatically.
It takes up to 11s from when disconnection state is restored till when measured
temperature value is stored into CH
Un\G18).
(d) The state of Disconnection state monitor flag (Un\G49), Disconnection state
signal (XC), and "ALM" LED remains, which means the state of disconnection
detection, remains even when disconnection state is restored. Turn on Error clear
request (YF).
(e) For operating the warning output function in disconnection and restoration, refer
to Section 3.2.4.
Maximum 11s
Normal
Disconnected
Normal(0)
Measured
Measured
temperature
temperature value (in
value
a gradual decline)
Measured temperature value (Un\G11 to Un\G18).
Measured temperature value (Un\G11 to
Maximum 11s
Normal
Disconnected(1)
Conversion setting for
disconnection state value
Normal(0)
Measured
temperature
value

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gx configurator-tiQ68td-g-h02

Table of Contents