Warning Output Enable/Disable Setting (Un\G46) - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.13
Enable/disable state of warning output for process alarm or rate alarm is set for each
channel.
(1) Setting methods
(2) Default value
3
- 46
3.4 Buffer Memory

3.4.13 Warning output enable/disable setting (Un\G46)

Warning output enable/disable setting (Un\G46)
(a) Warning output enable/disable setting is set for the corresponding channels in the
following figure.
b15 b14 b13 b12
CH8 CH7 CH6 CH5
Rate alaram setting
Figure 3.30 Setting of Warning output enable/disable setting (Un\G46)
(b) Turn on Operating condition setting request (Y9) to activate the setting.
Both process alarm and rate alarm are set to "Disable" for all channels (FFFF
b11 b10
b9
b8
b7
CH4 CH3 CH2 CH1
CH8 CH7 CH6 CH5
0: Enable, 1: Disable
b6
b5
b4
b3
b2
CH4 CH3 CH2 CH1
Process alarm setting
b1
b0
).
H