Disconnection state is detectable for each channel.
(1) Data storage
(2) How to clear flag
3
- 50
3.4 Buffer Memory

3.4.16 Disconnection state monitor flag (Un\G49) (Q68TD-G-H01only)

Disconnection state monitor flag (Un\G49) (Q68TD-G-H01only)
(a) The bit of the corresponding channel turns on (changes to "1") when the
disconnection state of a thermocouple or compensating lead wire is checked.
b15 b14 b13 b12 b11 b10
0
0
0
0
Data for b8 to b15 is fixed to "0".
Figure 3.33 Storage of Disconnection state monitor flag (Un\G49)
(b) Conversion for the channels not disconnected is continued.
(a) Check the sensor connection state of disconnection detection channels.
(b) When Operating condition setting request (Y9) or Error clear request (YF) is
turned on, this flag will be cleared.
When the signal turns on in disconnection state, the bit of the corresponding
channel turns on (changes to "1") again.
b9
b8
b7
0
0
0
0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
b6
b5
b4
b3
b2
0: Normal
1: Disconnected
b1