Range Reference Table (Q68Td-G-H01) - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

7
ONLINE MODULE CHANGE
7.4.2
Address (Decimal)
CH1
CH2
CH3
CH4
CH5
190
198
206
214
222
191
199
207
215
223
192
200
208
216
224
193
201
209
217
225
194
202
210
218
226
195
203
211
219
227
196
204
212
220
228
197
205
213
221
229
(1) Compare the factory default offset value with the reference value F89B
(2) Compare the factory default gain value with the reference value 3B22
(3) Compare the user range settings offset value with the value obtained from the
(4) Compare the user range settings gain value with the value obtained from the
(5) Obtain the chart of standard thermal electromotive force, complying with JIS C
(6) Obtain the chart of standard thermal electromotive force, complying with JIS C
7
- 35
7.4 Range Reference Table

7.4.2 Range reference table (Q68TD-G-H01)

Range reference table (Q68TD-G-H01)
CH6
CH7
CH8
230
238
246
Factory default offset value
231
239
247
Factory default gain value
232
240
248
User range settings offset value
233
241
249
User range settings gain value
234
242
250
User range settings thermal EMF offset value
235
243
251
User range settings thermal EMF offset value
236
244
252
User range settings thermal EMF gain value
237
245
253
User range settings thermal EMF gain value
following expression.
User range settings thermal
(Digital value) =
EMF offset value ( V)
following expression.
User range settings thermal
(Digital value) =
EMF gain value ( V)
1602-1995 and IEC584-1, or IEC584-2, for the user range settings offset
thermal electromotive force value. Then, compare the value with the offset
setting temperature set by the user.
1602-1995 and IEC584-1, or IEC584-2, for the user range settings gain
thermal electromotive force value. Then, compare the value with the gain
setting temperature set by the user.
POINT
The chart of standard thermal electromotive force compliant with JIS C 1602-1995
and IEC584-1, or IEC584-2 needs to be arranged by the user.
Description
Digital value for offset value set prior to
shipment (Reference value F89B
Digital value for gain value set prior to
shipment (Reference value 3B22
Digital value for user-set offset value (Refer to
(3))
Digital value for user-set gain value (Refer to
(4))
(L)
Thermal EMF for user-set offset set
temperature ( V unit) (Refer to (5))
(H)
(L)
Thermal EMF for user-set gain set temperature
( V unit) (Refer to (6))
(H)
90909
90909
Reference value
)
H
)
H
.
H
.
H
32767
32767